Old System: Propane 3-zone boiler with 40 gallon standard vented, DHW tank
New System: 4-ton Hydron Module Geothermal Heat Pump with desuperheater tied into Rinnai tankless DHW system
Configuration: horizontal, closed loop water-to-air
Loops: 4 - 3/4" X 800' HDPE piping loops runs installed in 4 - 3' (W) X 6' - 8' (D) trenches